<v Jon Lester>Hello and welcome to Buildings of
Tomorrow.

2
00:00:12.819 --> 00:00:16.319
<v Jon Lester>My name is Jon Lester, and today's episode
is another buzzword buster.

3
00:00:16.510 --> 00:00:20.299
<v Jon Lester>So if you haven't heard one of these
episodes from us in the past, they're a

4
00:00:20.299 --> 00:00:25.670
<v Jon Lester>slightly longer format, and basically we
pick one of, you know, the topics that we

5
00:00:25.670 --> 00:00:30.290
<v Jon Lester>discuss within our normal episodes, and we
just have a look at a lot of the terms

6
00:00:30.290 --> 00:00:34.220
<v Jon Lester>and a lot of the phrases that you hear in
the industry and run through with an

7
00:00:34.220 --> 00:00:34.790
<v Jon Lester>expert.

8
00:00:35.180 --> 00:00:40.909
<v Jon Lester>To give a brief description and a
definition of those terms, you know, there are so

9
00:00:40.909 --> 00:00:42.750
<v Jon Lester>many things changing in our industry.

10
00:00:43.310 --> 00:00:47.189
<v Jon Lester>We hear so many terms that perhaps we
don't have a full understanding of what they

11
00:00:47.189 --> 00:00:47.630
<v Jon Lester>mean.

12
00:00:48.029 --> 00:00:50.639
<v Jon Lester>So that is why the buzzword buster exists.

13
00:00:50.909 --> 00:00:53.810
<v Jon Lester>And today we are talking about hydronics.

14
00:00:54.430 --> 00:00:58.330
<v Jon Lester>I'm joined by Chris Coop, who is an expert
in HVAC theory and hydronics.

15
00:00:58.430 --> 00:01:00.130
<v Jon Lester>Chris, thank you very much for joining us.

16
00:01:00.759 --> 00:01:04.379
<v Chris Kopp>Hi John, thank you very much for having me
in this episode.

17
00:01:04.680 --> 00:01:06.620
<v Jon Lester>It is always a pleasure recorded from
home.

18
00:01:06.879 --> 00:01:09.059
<v Jon Lester>We keep charging no matter what happens
outside.

19
00:01:11.800 --> 00:01:12.139
<v Jon Lester>Perfect.

20
00:01:12.279 --> 00:01:15.639
<v Jon Lester>So, so today is a buzzword buster, as I
mentioned, hydronics is the topic.

21
00:01:15.760 --> 00:01:17.029
<v Jon Lester>We're going to dive straight in.

22
00:01:17.120 --> 00:01:18.989
<v Jon Lester>We've, we've taken a slightly different
approach here.

23
00:01:19.040 --> 00:01:22.639
<v Jon Lester>We want to keep it a little organized
because a lot of these terms really do refer

24
00:01:22.639 --> 00:01:24.360
<v Jon Lester>to each other or related to each other.

25
00:01:24.800 --> 00:01:30.360
<v Jon Lester>So we're going to start and run through a
bunch of different hydronic buzzwords, and

26
00:01:30.360 --> 00:01:37.250
<v Jon Lester>where we're going to start, uh, is at, uh,
uh, Something that we, we've mentioned

27
00:01:37.250 --> 00:01:41.160
<v Jon Lester>a few times, we haven't quite got into
detail, and the next thing that I have on the

28
00:01:41.160 --> 00:01:44.470
<v Jon Lester>list after our discussions is plant
characteristics.

29
00:01:46.389 --> 00:01:46.940
<v Chris Kopp>Yes.

30
00:01:47.190 --> 00:01:54.190
<v Chris Kopp>So, this basically is, is a, is an
additional topic with relation to these

31
00:01:54.190 --> 00:01:58.959
<v Chris Kopp>proportional laws because the plant
characteristic is a curve.

32
00:01:59.790 --> 00:02:05.080
<v Chris Kopp>That is based on the 2nd proportional law
and it just shows basically the

33
00:02:05.080 --> 00:02:11.179
<v Chris Kopp>relationship between the resistance and
the volumetric flow in a hydronic network

34
00:02:11.320 --> 00:02:13.179
<v Chris Kopp>and because it goes by the square.

35
00:02:13.440 --> 00:02:19.919
<v Chris Kopp>It is a parabolic curve, and when we draw
a graph with, let's say the volume flow on

36
00:02:19.919 --> 00:02:26.630
<v Chris Kopp>the x axis and the resistance on the y
axis, then you can show how

37
00:02:26.630 --> 00:02:31.440
<v Chris Kopp>your network behaves by drawing this
parabolic curve, and that's what we call the

38
00:02:31.440 --> 00:02:32.740
<v Chris Kopp>plant characteristic.

39
00:02:33.800 --> 00:02:39.399
<v Jon Lester>And how does that or how can that be
applied to a smaller part of the system, the

40
00:02:39.399 --> 00:02:41.059
<v Jon Lester>partial plant characteristic?

41
00:02:41.470 --> 00:02:42.440
<v Chris Kopp>Yes, so.

42
00:02:43.119 --> 00:02:48.500
<v Chris Kopp>When we say plant characteristic, we
normally mean how does the total system behave.

43
00:02:48.610 --> 00:02:54.169
<v Chris Kopp>So when we look at the at the total
circuit from the producer with the supply lines

44
00:02:54.169 --> 00:03:00.690
<v Chris Kopp>all the way out to the consumer and then
back, we could say with the maximum volume

45
00:03:00.690 --> 00:03:05.770
<v Chris Kopp>flow and the maximum resistance we can
derive basically how does the complete system

46
00:03:05.770 --> 00:03:06.350
<v Chris Kopp>behave.

47
00:03:06.770 --> 00:03:13.059
<v Chris Kopp>But very often we have to break it down
and look only at Parts of the piping or only

48
00:03:13.059 --> 00:03:19.820
<v Chris Kopp>look at certain components, and this
second proportional law applies on

49
00:03:19.820 --> 00:03:24.899
<v Chris Kopp>one hand to the complete system set up,
but it also applies to an individual

50
00:03:24.899 --> 00:03:25.580
<v Chris Kopp>component.

51
00:03:25.899 --> 00:03:31.899
<v Chris Kopp>So for example, if you have a heating coil
in an air handling unit and it has a

52
00:03:31.899 --> 00:03:34.949
<v Chris Kopp>certain resistance at the design flow.

53
00:03:35.270 --> 00:03:41.809
<v Chris Kopp>Then its flow, its resistance also goes
back by the square when we lower the flow,

54
00:03:42.229 --> 00:03:42.649
<v Chris Kopp>so.

55
00:03:43.220 --> 00:03:48.139
<v Chris Kopp>By that we can break down a system to all
its separate parts, to its components, to

56
00:03:48.139 --> 00:03:54.339
<v Chris Kopp>different pipe sections, and then
basically draw or envision such a

57
00:03:54.339 --> 00:04:00.100
<v Chris Kopp>parabolic behavior based on the second
proportional law for these individual parts

58
00:04:00.339 --> 00:04:05.300
<v Chris Kopp>and add them up and stack them up in
whichever way it makes sense to consider

59
00:04:05.300 --> 00:04:10.220
<v Chris Kopp>certain behaviors, and this is very often
important when we look at part load

60
00:04:10.220 --> 00:04:10.539
<v Chris Kopp>conditions.

61
00:04:10.789 --> 00:04:17.630
<v Chris Kopp>Because then we have to consider how do
certain parts of our system react to a

62
00:04:17.630 --> 00:04:23.350
<v Chris Kopp>reduced flow and maybe other parts react
in a different way and then you can really

63
00:04:23.350 --> 00:04:28.799
<v Chris Kopp>think about, and now what is the situation
when I only have 60% of flow.

64
00:04:29.299 --> 00:04:32.429
<v Chris Kopp>What does that mean for my main
distribution lines?

65
00:04:32.489 --> 00:04:34.910
<v Chris Kopp>What does it mean for a certain consumer?

66
00:04:35.160 --> 00:04:40.350
<v Chris Kopp>And that then helps very often to figure
out how can we handle that.

67
00:04:40.690 --> 00:04:42.190
<v Chris Kopp>With our controls.

68
00:04:44.040 --> 00:04:44.970
<v Jon Lester>Great, thank you.

69
00:04:45.640 --> 00:04:51.359
<v Jon Lester>Uh, now let's get into, you know, we've
talked a lot about variable volumetric flow,

70
00:04:51.760 --> 00:04:52.279
<v Jon Lester>uh.

71
00:04:52.920 --> 00:04:57.660
<v Jon Lester>To deliver this variable volumetric flow
at a system level, we rely on the pumps,

72
00:04:57.670 --> 00:04:59.359
<v Jon Lester>and we have variable speed pumps.

73
00:04:59.440 --> 00:05:03.799
<v Jon Lester>Can you give us a quick definition or
confirmation of what we mean when we say

74
00:05:03.799 --> 00:05:05.320
<v Jon Lester>variable speed pumps?

75
00:05:06.470 --> 00:05:13.059
<v Chris Kopp>Yes, as you just said, by trying to have
variable flow throughout, let's say the

76
00:05:13.059 --> 00:05:18.989
<v Chris Kopp>whole network, then of course we need to
enlist the help of pumps that can adjust to

77
00:05:18.989 --> 00:05:20.359
<v Chris Kopp>changing conditions.

78
00:05:20.630 --> 00:05:25.820
<v Chris Kopp>And when I said before that we now have
some preferred hydraulic circuits.

79
00:05:26.480 --> 00:05:33.029
<v Chris Kopp>And we want to run variable flow, of
course, this only became possible once

80
00:05:33.029 --> 00:05:39.190
<v Chris Kopp>variable speed pumps or variable speed
drives for bigger pumps became available and

81
00:05:39.200 --> 00:05:44.609
<v Chris Kopp>and became also available at reasonable
cost to be put into place.

82
00:05:44.779 --> 00:05:50.170
<v Chris Kopp>But today I would say it, it is standard
even in in areas where you want to run

83
00:05:50.170 --> 00:05:51.470
<v Chris Kopp>constant volume flow.

84
00:05:52.140 --> 00:05:56.380
<v Chris Kopp>Today you probably have a variable speed
pump that you then just set to a constant

85
00:05:56.380 --> 00:06:00.589
<v Chris Kopp>speed because it's much, much easier to
buy such a pump than another one.

86
00:06:01.140 --> 00:06:07.459
<v Chris Kopp>So we need variable speed pumps, and I
think the only thing that we have to keep in

87
00:06:07.459 --> 00:06:14.390
<v Chris Kopp>mind, unfortunately, We cannot control
them between 0 and 100% of

88
00:06:14.390 --> 00:06:15.190
<v Chris Kopp>volume flow.

89
00:06:15.470 --> 00:06:22.390
<v Chris Kopp>We can only drive them down maybe to about
30 or 25% of the maximum flow.

90
00:06:22.630 --> 00:06:23.670
<v Chris Kopp>And below that.

91
00:06:25.089 --> 00:06:30.209
<v Chris Kopp>We cannot go further down because of the
way the EC motors and the variable speed

92
00:06:30.209 --> 00:06:35.929
<v Chris Kopp>drives are designed and, and, and, and
work, and we just have to keep in mind once

93
00:06:35.929 --> 00:06:42.559
<v Chris Kopp>we Turn on such a pump, it will always run
at least, let's say at 25%

94
00:06:42.559 --> 00:06:47.899
<v Chris Kopp>of the maximum flow, and this is also
something that needs to be then considered

95
00:06:47.899 --> 00:06:52.980
<v Chris Kopp>when we select the pumps, you know,
sometimes it might even make sense to have two

96
00:06:52.980 --> 00:06:54.959
<v Chris Kopp>separate pumps at different sizes

97
00:06:55.380 --> 00:06:59.320
<v Chris Kopp>to, to really take advantage of varying
the flow.

98
00:07:00.089 --> 00:07:02.369
<v Chris Kopp>Almost between 0 and 100%.

99
00:07:03.980 --> 00:07:04.660
<v Jon Lester>OK, perfect.

100
00:07:04.700 --> 00:07:10.399
<v Jon Lester>And, and There are different ways for us
to control these variable speed pumps.

101
00:07:10.450 --> 00:07:15.690
<v Jon Lester>So let's look now at the next two that
we'd like to talk about, or the next 3 delta

102
00:07:15.690 --> 00:07:21.850
<v Jon Lester>P constant, deltaP proportional, and
deltaP constant at the end point of the plant.

103
00:07:23.299 --> 00:07:30.100
<v Chris Kopp>Yes, so with variable speed bumps, pumps
that come, there are also

104
00:07:30.100 --> 00:07:30.839
<v Chris Kopp>different.

105
00:07:31.609 --> 00:07:36.570
<v Chris Kopp>Approach is how we can control them
because of course we want to vary the speed in

106
00:07:36.570 --> 00:07:43.510
<v Chris Kopp>order to adjust to the flow, but also in
order to adjust to the changing resistance

107
00:07:43.510 --> 00:07:47.359
<v Chris Kopp>in our network because as we discussed
before with the proportional laws or the

108
00:07:47.359 --> 00:07:48.260
<v Chris Kopp>affinity laws.

109
00:07:48.529 --> 00:07:54.089
<v Chris Kopp>So let's focus on the first two, the delta
P constant and the delta P proportional,

110
00:07:54.290 --> 00:08:00.899
<v Chris Kopp>because these are two strategies or
approaches that are also Implemented

111
00:08:01.239 --> 00:08:07.660
<v Chris Kopp>by the pump manufacturers, these are two
approaches that can easily be selected on a

112
00:08:08.200 --> 00:08:13.359
<v Chris Kopp>controlled pump, electronically controlled
pump, directly by hitting a button or by

113
00:08:13.359 --> 00:08:18.519
<v Chris Kopp>selecting this strategy, let's say in an
app that you have on your mobile phone

114
00:08:18.519 --> 00:08:23.899
<v Chris Kopp>or so, and delta P constant means just
that it maintains.

115
00:08:25.160 --> 00:08:30.859
<v Chris Kopp>The pressure or the pump head as we say it
that the pump brings at design, it

116
00:08:31.200 --> 00:08:33.520
<v Chris Kopp>maintains always this amount of pressure.

117
00:08:33.599 --> 00:08:37.309
<v Chris Kopp>It doesn't go above, but it also doesn't
go below.

118
00:08:37.359 --> 00:08:43.840
<v Chris Kopp>It says, for example, we have 7 m of water
column that we need as pump head

119
00:08:44.099 --> 00:08:50.039
<v Chris Kopp>at design, and the pump always maintains
that amount of pressure whether it's needed

120
00:08:50.039 --> 00:08:50.559
<v Chris Kopp>or not.

121
00:08:51.179 --> 00:08:57.559
<v Chris Kopp>And in order to maintain that at lower
volume flows, it will reduce the speed

122
00:08:57.929 --> 00:08:59.340
<v Chris Kopp>somewhat, a little bit.

123
00:09:00.049 --> 00:09:06.890
<v Chris Kopp>Unfortunately, this only has, let's say, a
small impact on the power

124
00:09:06.890 --> 00:09:13.260
<v Chris Kopp>consumption, maybe depending on the pump,
between 10 to let's say 25%.

125
00:09:14.599 --> 00:09:21.130
<v Chris Kopp>Because When we look at the whole
situation and at this parabolic curve of the plant

126
00:09:21.130 --> 00:09:27.289
<v Chris Kopp>characteristic, when you envision such a
parabolic curve, we know that it goes down

127
00:09:27.289 --> 00:09:33.729
<v Chris Kopp>rather dramatically at low flows, which
means then maintaining always the constant

128
00:09:33.729 --> 00:09:39.919
<v Chris Kopp>pump head is a waste because then our
control valve has to take care of the

129
00:09:39.919 --> 00:09:40.489
<v Chris Kopp>difference.

130
00:09:40.880 --> 00:09:46.969
<v Chris Kopp>Which basically throttles it off as much
as it can and that of course is not very

131
00:09:46.969 --> 00:09:51.570
<v Chris Kopp>efficient from the energy perspective so
that's why We and also the pump

132
00:09:51.570 --> 00:09:57.960
<v Chris Kopp>manufacturers say rather than maintaining
a constant pump head, why don't we lower

133
00:09:58.059 --> 00:10:01.020
<v Chris Kopp>the provided pump head continuously.

134
00:10:02.239 --> 00:10:09.179
<v Chris Kopp>Most of the time to a point where at very
low flow we reach about half of what

135
00:10:09.200 --> 00:10:15.219
<v Chris Kopp>we had as a palm pet at design, and that
is then often called delta P proportional

136
00:10:15.489 --> 00:10:21.409
<v Chris Kopp>and Because we lowered the pressure that
is provided by the pump continuously

137
00:10:22.510 --> 00:10:26.630
<v Chris Kopp>as we lower the flow, this of course is
more energy efficient.

138
00:10:26.830 --> 00:10:33.469
<v Chris Kopp>And with that approach, if you look at,
at, at average, let's say volume flows of

139
00:10:33.469 --> 00:10:38.090
<v Chris Kopp>about 50%, we can reduce the power
consumption already.

140
00:10:39.200 --> 00:10:45.479
<v Chris Kopp>Quite interestingly, between let's say 25
to maybe even up to 40, 45%

141
00:10:45.479 --> 00:10:50.520
<v Chris Kopp>compared to what the pump pulls or draws
uh at design.

142
00:10:51.690 --> 00:10:58.130
<v Chris Kopp>And these, as I said, are standard
approaches that you can normally also select on

143
00:10:58.130 --> 00:11:01.169
<v Chris Kopp>an electronically controlled pump as a
strategy.

144
00:11:02.400 --> 00:11:09.390
<v Chris Kopp>Now the next two that I would like to talk
about are most often then implemented or

145
00:11:09.390 --> 00:11:15.500
<v Chris Kopp>are in need of a billing automation
system, and the first one is that we say

146
00:11:16.239 --> 00:11:22.640
<v Chris Kopp>let's have delta P constant somewhere at
the end point of the plan, meaning across

147
00:11:22.640 --> 00:11:24.780
<v Chris Kopp>the consumer and the control valve.

148
00:11:25.239 --> 00:11:30.109
<v Chris Kopp>So that means we try to figure out how
much pressure do we need out there at any

149
00:11:30.109 --> 00:11:30.799
<v Chris Kopp>given time.

150
00:11:31.250 --> 00:11:36.950
<v Chris Kopp>And this is what we control too, and
experience shows this is usually

151
00:11:38.750 --> 00:11:41.919
<v Chris Kopp>much lower than what we would achieve with
delta P proportional.

152
00:11:42.010 --> 00:11:48.380
<v Chris Kopp>So it gives us an additional saving
possibility, but of course we somehow have to

153
00:11:48.380 --> 00:11:54.969
<v Chris Kopp>measure the resistance out there and the
pressure that we provide at the consumer,

154
00:11:55.039 --> 00:11:57.530
<v Chris Kopp>which means we have to have ways to
connect that.

155
00:11:58.270 --> 00:12:01.390
<v Chris Kopp>To the building automation system and then
drive it from there.

156
00:12:01.869 --> 00:12:06.700
<v Chris Kopp>And that's something a pump itself cannot
do because it has no means to measure

157
00:12:06.700 --> 00:12:12.590
<v Chris Kopp>somewhere out in the, in the hydraulic
circuit, what the actual pressure provided

158
00:12:12.590 --> 00:12:13.690
<v Chris Kopp>out there is.

159
00:12:13.950 --> 00:12:17.440
<v Chris Kopp>So that's why I said we need to rely on a
building automation system.

160
00:12:17.869 --> 00:12:22.590
<v Chris Kopp>And that gives us an an additional
advantage to the standard approaches.

161
00:12:23.200 --> 00:12:25.770
<v Chris Kopp>If we want to do it the best way we can.

162
00:12:26.450 --> 00:12:33.239
<v Chris Kopp>We should do it demand-based, and that's a
term that is often heard and used, but

163
00:12:33.659 --> 00:12:39.059
<v Chris Kopp>demand-based means we try to find a way to
figure out.

164
00:12:40.090 --> 00:12:46.760
<v Chris Kopp>What the consumers currently need, and I
say exactly consumers, not just

165
00:12:46.760 --> 00:12:53.690
<v Chris Kopp>one, several, because we then can derive
from, example, the valve positions, what

166
00:12:53.690 --> 00:12:59.469
<v Chris Kopp>is their need, and if we see, for example,
that all these valves are throttling down

167
00:12:59.469 --> 00:13:05.760
<v Chris Kopp>to maybe 40%, this is a clear indicator
that the pump, At

168
00:13:05.760 --> 00:13:09.950
<v Chris Kopp>the producer puts way too much pressure
into our

169
00:13:09.950 --> 00:13:12.840
<v Chris Kopp>network because all the valves have to
hold against that pressure.

170
00:13:13.479 --> 00:13:18.799
<v Chris Kopp>So by knowing that we then can go back
through the building automation system and

171
00:13:18.799 --> 00:13:25.520
<v Chris Kopp>continuously lower the pump speed, for
example, by resetting the pressure

172
00:13:25.520 --> 00:13:28.250
<v Chris Kopp>differential set point for this pump.

173
00:13:28.729 --> 00:13:34.880
<v Chris Kopp>And the beauty of it is that It reacts to
the changes in the dynamic network because

174
00:13:34.890 --> 00:13:41.500
<v Chris Kopp>we talked before and said our networks
have a dynamic behavior and

175
00:13:41.500 --> 00:13:47.200
<v Chris Kopp>sometimes that leads to oversupply and
sometimes that leads to undersupply.

176
00:13:47.460 --> 00:13:50.619
<v Chris Kopp>With demand-based approach, this is no
longer true.

177
00:13:50.900 --> 00:13:56.059
<v Chris Kopp>We always have exactly what we need out
there at any given consumer because we

178
00:13:56.059 --> 00:13:56.840
<v Chris Kopp>always check.

179
00:13:57.469 --> 00:14:03.789
<v Chris Kopp>Which consumer has the biggest demand, and
this one then drives the pump speed and

180
00:14:03.789 --> 00:14:08.549
<v Chris Kopp>with that the pressure that the pump
provides, and this is the most energy efficient

181
00:14:08.549 --> 00:14:09.309
<v Chris Kopp>way of doing it.

182
00:14:09.390 --> 00:14:16.020
<v Chris Kopp>But of course it needs a communicating
building automation system because

183
00:14:16.030 --> 00:14:20.030
<v Chris Kopp>somehow we have to get the information
from the different consumers throughout the

184
00:14:20.030 --> 00:14:20.650
<v Chris Kopp>building.

185
00:14:21.280 --> 00:14:21.289
<v Chris Kopp>Thank

186
00:14:21.289 --> 00:14:21.500
<v Jon Lester>you.

187
00:14:22.030 --> 00:14:23.289
<v Jon Lester>So we covered quite a bit there.

188
00:14:23.590 --> 00:14:30.559
<v Jon Lester>We looked at 22 different, let's say,
variable speed pump control strategies

189
00:14:30.559 --> 00:14:35.070
<v Jon Lester>that are based within the pump themselves
delta P constant, where you're just

190
00:14:35.070 --> 00:14:40.469
<v Jon Lester>maintaining a set point around the pump
head, delta P proportional where you

191
00:14:40.469 --> 00:14:46.669
<v Jon Lester>continually try and step that pump head
set point back while still maintaining.

192
00:14:47.659 --> 00:14:52.390
<v Jon Lester>the required flow, which certainly gives
you more advantages than the delta P

193
00:14:52.390 --> 00:14:58.960
<v Jon Lester>constant, but that next level again by
involving a building automation system to

194
00:14:59.380 --> 00:15:02.150
<v Jon Lester>to actually bring some transparency from
the field.

195
00:15:02.539 --> 00:15:05.400
<v Jon Lester>And the first one you mentioned was the
delta P constant at the endpoint.

196
00:15:05.510 --> 00:15:10.789
<v Jon Lester>So picking the part of the of the system
which is the furthest away as an example

197
00:15:10.789 --> 00:15:13.809
<v Jon Lester>from the pump and making sure that the
delta P.

198
00:15:14.510 --> 00:15:21.390
<v Jon Lester>Provided at that point is, is up to the
minimum or the expected requirements,

199
00:15:21.880 --> 00:15:26.599
<v Jon Lester>which gives us some transparency at the
very, at the end point, and we just assume

200
00:15:26.599 --> 00:15:31.669
<v Jon Lester>by saying if you're, if the people
furthest away are getting enough water, then we

201
00:15:31.669 --> 00:15:33.919
<v Jon Lester>assume everyone else is getting enough
water as well.

202
00:15:34.409 --> 00:15:39.210
<v Jon Lester>Um, and then the last one, and then the
last one you mentioned was the best, which

203
00:15:39.210 --> 00:15:43.289
<v Jon Lester>is not just to look at one single point in
the system, but to look at every point in

204
00:15:43.289 --> 00:15:48.809
<v Jon Lester>the system where you can not just verify
that perhaps the flow is correct, but if

205
00:15:48.809 --> 00:15:55.770
<v Jon Lester>you see some consistent behavior from
those control systems to say my

206
00:15:55.770 --> 00:16:00.489
<v Jon Lester>whole system is at 50%, that means I'm
providing way too much water, so I can dial

207
00:16:00.489 --> 00:16:01.969
<v Jon Lester>back even more my set point.

208
00:16:02.179 --> 00:16:08.380
<v Jon Lester>Because if the valve is open to 100% in
every place and I'm providing the right

209
00:16:08.380 --> 00:16:10.840
<v Jon Lester>amount of water, that's my ideal
situation.

210
00:16:11.260 --> 00:16:12.059
<v Jon Lester>Nothing is wasted.

211
00:16:12.210 --> 00:16:16.900
<v Jon Lester>There is no pressure that has to be washed
by the valves and no wasted energy at the

212
00:16:16.900 --> 00:16:17.280
<v Jon Lester>pump.

213
00:16:17.700 --> 00:16:23.059
<v Chris Kopp>Yes, exactly, exactly, and I think with
today's, let's say, building automation

214
00:16:23.059 --> 00:16:28.739
<v Chris Kopp>system setups where we Normally have,
let's say in in an office building or so where

215
00:16:28.739 --> 00:16:34.469
<v Chris Kopp>we have individual room control for
heating, cooling, ventilation, and these

216
00:16:34.469 --> 00:16:41.239
<v Chris Kopp>controllers are communicating across
standard networks like KNX or Baknet or so,

217
00:16:42.020 --> 00:16:46.940
<v Chris Kopp>then this demand-based pump control is
just basically

218
00:16:47.409 --> 00:16:53.289
<v Chris Kopp>A rather small engineering effort that has
to be put into the system, but you gain

219
00:16:53.289 --> 00:16:58.770
<v Chris Kopp>quite a bit with regards to pump
efficiency, and I think this is always worthwhile

220
00:16:58.770 --> 00:16:59.320
<v Chris Kopp>to do.

221
00:16:59.989 --> 00:17:00.489
<v Jon Lester>Beautiful.

222
00:17:01.049 --> 00:17:05.609
<v Jon Lester>Now the last, the last word on the list
that I'd like to cover is something that we

223
00:17:05.609 --> 00:17:10.250
<v Jon Lester>just mentioned then when we were
describing different strategies to, to.

224
00:17:11.180 --> 00:17:15.089
<v Jon Lester>To control a variable speed pump is the
pump head because we mentioned the pump head

225
00:17:15.089 --> 00:17:17.869
<v Jon Lester>but we didn't really talk about what we
mean by that phrase.

226
00:17:18.298 --> 00:17:24.178
<v Chris Kopp>Yes, so it's a, it's a common term that is
used in the industry, and it basically

227
00:17:24.178 --> 00:17:27.958
<v Chris Kopp>means the pressure a pump provides to the
network.

228
00:17:28.338 --> 00:17:31.759
<v Chris Kopp>And pumped is, is just a term that is used
for that.

229
00:17:31.779 --> 00:17:37.379
<v Chris Kopp>And very often when we talk about pumpped,
we also use the unit's meter of water

230
00:17:37.379 --> 00:17:43.659
<v Chris Kopp>column, which is also kind of a
traditional unit, you know, when you look at the SI

231
00:17:43.659 --> 00:17:47.678
<v Chris Kopp>units, you would rather talk in
kilopascals or millibars or bar.

232
00:17:48.069 --> 00:17:54.969
<v Chris Kopp>But a lot of people have a feeling for
what does 1 m or 7 m of

233
00:17:54.969 --> 00:18:00.790
<v Chris Kopp>water column mean with relation to a
system set up, because they, they have been,

234
00:18:00.930 --> 00:18:07.410
<v Chris Kopp>they are, they are used to that and have
established a certain, let's say, internal

235
00:18:07.410 --> 00:18:11.869
<v Chris Kopp>feeling for that, and they can then
envision what it means in their situation.

236
00:18:12.050 --> 00:18:14.660
<v Chris Kopp>And so the pump head is often talked in.

237
00:18:15.140 --> 00:18:19.540
<v Chris Kopp>Meters per water column and when you
envision it, it just means the pump would be

238
00:18:19.540 --> 00:18:26.410
<v Chris Kopp>able to pump the water from a level zero
all the way up to 7 m.

239
00:18:26.650 --> 00:18:33.310
<v Chris Kopp>What we have to keep in mind these meter
of water columns are just a picture

240
00:18:33.619 --> 00:18:40.040
<v Chris Kopp>because today we have closed circuit
systems that are pressurized, so

241
00:18:40.459 --> 00:18:46.959
<v Chris Kopp>the The elevation that we have in a
building or so is not what influences this

242
00:18:46.959 --> 00:18:50.119
<v Chris Kopp>pressure that the pump has to provide the
pump pad.

243
00:18:50.839 --> 00:18:56.239
<v Chris Kopp>It's really driven by the resistance in
our network created by pipes, by components

244
00:18:56.239 --> 00:18:58.420
<v Chris Kopp>like heating coils, cooling coils, and so
on.

245
00:18:58.599 --> 00:18:59.839
<v Chris Kopp>But it's a common term.

246
00:19:00.160 --> 00:19:06.199
<v Chris Kopp>And even in catalogs of pump
manufacturers, they show the pressure of pumps in

247
00:19:06.199 --> 00:19:08.670
<v Chris Kopp>meters of water columns and label it pump.

248
00:19:08.869 --> 00:19:10.579
<v Chris Kopp>That's why we brought it up this way.

249
00:19:10.839 --> 00:19:11.760
<v Jon Lester>OK, perfect.

250
00:19:12.699 --> 00:19:13.619
<v Jon Lester>Chris, thank you so much.

251
00:19:13.660 --> 00:19:19.859
<v Jon Lester>We've covered a huge amount of different
terms, whether they're part of choosing,

252
00:19:20.140 --> 00:19:24.979
<v Jon Lester>selecting, and ensuring that we understand
correctly the valves that we're putting

253
00:19:24.979 --> 00:19:30.579
<v Jon Lester>within the system, the circuits that help
make up that system, or the system itself,

254
00:19:30.739 --> 00:19:36.930
<v Jon Lester>how we describe it, and how we look at the
way that we control the flow and the

255
00:19:36.930 --> 00:19:41.099
<v Jon Lester>different approaches that we have in
controlling the pumps that deliver that flow

256
00:19:41.099 --> 00:19:41.739
<v Jon Lester>and that pressure.

257
00:19:42.280 --> 00:19:44.969
<v Jon Lester>Thank you so much as always for joining
us.

258
00:19:45.369 --> 00:19:47.890
<v Jon Lester>Um, we very much enjoy it when you visit
me.

259
00:19:47.959 --> 00:19:51.880
<v Jon Lester>I, I get the feeling that we probably have
another one of these buzzword busters in

260
00:19:51.880 --> 00:19:58.319
<v Jon Lester>us when we want to talk about other
components of, of the, uh, of the HVAC systems.

261
00:19:58.689 --> 00:19:58.770
<v Jon Lester>Yeah,

262
00:19:58.849 --> 00:20:03.869
<v Chris Kopp>I think there is more to discuss besides
hydraulics, you know, I think there are

263
00:20:04.089 --> 00:20:07.410
<v Chris Kopp>such terms in, in the heating part, in the
cooling part.

264
00:20:07.633 --> 00:20:13.152
<v Chris Kopp>And also in the ventilation and air
conditioning part, for example, VAV and things

265
00:20:13.152 --> 00:20:17.672
<v Chris Kopp>like that that are maybe worthwhile to
discuss at another time.

266
00:20:18.032 --> 00:20:18.672
<v Jon Lester>I believe so.

267
00:20:18.713 --> 00:20:24.873
<v Jon Lester>I think that if we, not to scare anyone,
but if we have a VAV, an AHU and an FCU

268
00:20:24.873 --> 00:20:29.113
<v Jon Lester>discussion at some point, that will give
us a good start for another good buzzword

269
00:20:29.113 --> 00:20:29.792
<v Jon Lester>buster for sure.

270
00:20:29.916 --> 00:20:30.385
<v Jon Lester>Yes.

271
00:20:30.796 --> 00:20:35.336
<v Jon Lester>So thank you, thank you again, Chris, uh,
and, uh, thank you to all of you out there

272
00:20:35.336 --> 00:20:37.196
<v Jon Lester>for listening, uh, to this episode.

273
00:20:37.355 --> 00:20:40.156
<v Jon Lester>Please feel free to share, like and
comment on this episode.

274
00:20:40.316 --> 00:20:43.526
<v Jon Lester>Subscribe to us on whichever channel
you're listening to us right now.

275
00:20:43.875 --> 00:20:44.936
<v Jon Lester>Uh, remember to share.

276
00:20:45.375 --> 00:20:50.076
<v Jon Lester>Uh, and as always, we very much appreciate
your time in joining us, and we look

277
00:20:50.076 --> 00:20:51.276
<v Jon Lester>forward to seeing you again soon.

278
00:20:51.515 --> 00:20:52.015
<v Jon Lester>Thank you.